Automatic burner control DGAI. 70N Dungs 24 VAC for atmospheric gas burners

Automatic burner control DGAI. 70N Dungs
  • These automatic burner controls DGAI. 70N are suitable for igniting and monitoring atmospheric gas burners designed for intermittent operation. They have a start inhibiting function (EN 509) which becomes active in case of a power failure.
  • Flame monitoring by ionisation.
  • Program flow control by electronic timers.
  • Integrated cyclic spark ignition.
  • 24 VDC pilot gas valve.
  • 24 VDC main gas valve, 1st stage.
  • 24 VDC main gas valve, 2nd stage.
  • Ignition and flame monitoring with common electrode or with separate ignition and ionisation electrode.
  • Visual fault indication by LED.


Functional description DGAI. 70N

When the controller signals that heat is required, the ignition is activated after a waiting time of 3 seconds at start-up, and the pilot gas valve is opened. The fault LED blinks briefly to indicate that start-up is in progress. The ignition is switched off when the pilot flame signal is detected. At the end of the safety time (SZA), the main gas valve is opened if the flame is lit. The Mod. 90.3 TLL opens the main valve with a delay of 2 seconds after the pilot flame signal is detected.
If no flame is formed within the safety time, the ignition is switched off and the control locks in fault mode. If a loss of flame occurs during operation, all gas valves are switched off during the extinction safety time (SZB). The ignition is then disabled in the fault mode, or an attempt to restart the burner is made. In the case of a normal shut-down, the gas solenoid valves are closed. If a flame signal is detected before fuel release, start-up is disabled as long as the flame signal is applied.
The DGAI. 70N is additionally provided with an electronic interlock circuit (EN 509) which prevents an automatic restart during voltage restoration after a power voltage failure. In this case, the DGAI. 70N can be set in operation when power voltage is applied by switching the request switch off and on again.


Technical specifications

Type Code Voltage (V) Frequency (Hz) Power (VA) Degree of prot. Ambient temp. (oC) Fuse
DGAI. 70N Mod. 10.3 TLL 226132 24 VAC 50 5 IP 20 0÷60 6.3 A (slow)
10 A (fast)
DGAI. 70N Mod. 10.3 TLL S02 226244
DGAI. 70N Mod. 10.3 TLL S03 242018
DGAI. 70N Mod. 90.3 TLL 232217
DGAI. 70N Mod. 90.3 TLL S03 242019
DGAI. 70N Mod. 5.1 TCV 226134 24 VAC 50 5 IP 20 0÷60 6.3 A (slow)
10 A (fast)
DGAI. 70N Mod. 10.3 TCV 226133
DGAI. 70N Mod. 5.1 TVV 226135

 

Type Code Startup delay time AWZ (s) Startup safety period SZA (s) Operation safety period SZB (s) Fault indication Recycling
DGAI. 70N Mod. 10.3 TLL 226132 <3 <10 <3 Internal -
DGAI. 70N Mod. 10.3 TLL S02 226244 <10 <3 External -
DGAI. 70N Mod. 10.3 TLL S03 242018 <10 <3 External -
DGAI. 70N Mod. 90.3 TLL 232217 <90 <3 Internal -
DGAI. 70N Mod. 90.3 TLL S03 242019 <90 <3 External -
DGAI. 70N Mod. 5.1 TCV 226134 <5 <1 Internal YES
DGAI. 70N Mod. 10.3 TCV 226133 <10 <3 Internal YES
DGAI. 70N Mod. 5.1 TVV 226135 <5 <1 Internal -


Dimensions DGAI. 70N (mm)

dimensions DGAI. 70N - 1 dimensions DGAI. 70N - 2
For the images that aren't clear move the mouse over them to zoom.


Prices for controls DGAI. 70N

Code Type Prices without VAT
226132 Automatic burner control DGAI. 70N Mod. 10.3 TLL 0.00
226244 Automatic burner control DGAI. 70N Mod. 10.3 TLL S02 0.00
242018 Automatic burner control DGAI. 70N Mod. 10.3 TLL S03 0.00
232217 Automatic burner control DGAI. 70N Mod. 90.3 TLL 0.00
242019 Automatic burner control DGAI. 70N Mod. 90.3 TLL S03 0.00
226134 Automatic burner control DGAI. 70N Mod. 5.1 TCV 0.00
226133 Automatic burner control DGAI. 70N Mod. 10.3 TCV 0.00
226135 Automatic burner control DGAI. 70N Mod. 5.1 TVV 0.00
In case the price is missing or for a list of discounts contact us directly to receive an offer.