>> Automatic burner controls >> DGAI. 52FN WLE


Automatic burner control DGAI. 52FN Dungs with ignition control for gas burners with blower

Automatic burner control DGAI. 52FN WLE Dungs
  • These automatic burner controls DGAI. 52FN, 52FN WLE are designed for ignition control and monitoring for gas burners with fan for intermittent operation with capacities up to 350 kW. Suitable for condensing boilers that operate with atmospheric burners and fan exhaust. By purging at controlled shutdown residual gases are discharged.
  • Flame detection by ionization.
  • Program sequence control by electronic timers.
  • Electronic ignition with ignition transformer DZÜ 2.
  • Ignition and flame monitoring with common electrode or with separate ignition and ionisation.
  • Air monitoring.
  • DGAI. 52FN WLE is suitable for use on air heaters and ambient temperatures up to -15oC.
  • Classification EN 298 FTLLXN.


Functional description DGAI. 52FN

When the regulator receives a heat request, voltage is applied to the blower motor (provided that air pressure detector signals proper functioning). After a purge period (VSZ), the igniter and start valve are switched on. The igniter switches immediately off on receipt of the flame signal. If no flame is generated during the safety period interval of 5 seconds (SZA), fault interlock is performed. If a flame occurs when the regulator is switched on, the program sequence is blocked. On flame loss during operation, the gas valve is switched off within 1 second (SZB). During regulator or fault switch off, the blower runs out for 15 seconds.
 
Fault release: By means of an integrated button or externally via NOC from terminal 15 to N.
 
Ignition and flame detection using DZU 2
The ignition control system is integrated on the PCB. Approximately 5 ignition sparks are created per second at 200 V by capacitor discharge via a thyristor on the primary coil of the ignition transformer. This is increased to 10-15 kV by the ignition transformer. Plug the DZU 2 directly into the electrode which carries out ignition and flame detection. The DGAI. 52FN can be operated with separated ignition and monitoring electrodes for end-point monitoring. Tie the black wire of DZU 2 to ground and connect the monitoring electrode to terminal 8.


Technical specifications

Type Code Voltage (V) Frequency (Hz) Power consumption (VA) Degree of protection Ambient temperature (oC) Safety interval start (s)
DGAI. 52FN 215748 230 VAC 50 10 IP 40 0÷60 <5
DGAI. 52FN WLE 220436 -15÷60


Dimensions DGAI. 52FN WLE (mm)

Automatic burner control DGAI. 52FN
dimensions DGAI. 52FN - 1 dimensions DGAI. 52FN - 2

 

Ignition transformer DZU2
dimensions DZU2
Treceti cu mouse-ul peste imaginile care nu se vad in detaliu pentru a le mari.